Date: 2020-01-01 10:30 pm (UTC)
eta_ta: (0)
From: [personal profile] eta_ta
как всегда!
вы, конечно, знаете лучше архитектора, кот. проектирует коммерческие интерьеры так чтоб удовлетворяли законам и стандартам штатов.

нет, птичка.

по минимальному стандарту, lactation rooms are to contain:
*equipment - (1) sink with cold/hot water faucet; (1) refrigerator (could be undercounter); (1) arm- or lounge-chair; (1) table or counter surface of minimum 2'x 2'.
*interior area should be min 50sf, to accommodate ADA-compliant wheelchair' maneuvering circle of 60" and maintain 4'-6" clear in front of swing-in door
*power requirements:(1) dedicated quad (for breast pump, vacuum cleaner, humidifier, refrigerator)
* HVAC requirements: separate branch to be controlled by room-located (1) thermostat
* noise reduction requirements: partitions (walls) are to be state-approved acoustic type (to be extended to structure, not to suspended ceiling, contain acoustic insulation and sealant at floor and ceiling joints)
-door should be lockable from inside, with lever-type lockset
-finishes and furnishings to be Class A (II) fire-code compliant
-lighting level to be of min 45CA; if there is a window there must be a matte shade or curtain, operable from inside

как вы думаете, орлица вы наша, сколько всё это стОит?
PS
комнату лактации запрещается совмещать с туалетной комнатой.
This account has disabled anonymous posting.
If you don't have an account you can create one now.
HTML doesn't work in the subject.
More info about formatting

Profile

aka_human: (Default)
aka_human

July 2025

S M T W T F S
  12345
67 89101112
13141516171819
20212223242526
2728293031  

Style Credit

Expand Cut Tags

No cut tags
Page generated Aug. 1st, 2025 11:55 am
Powered by Dreamwidth Studios